Features
- Proven electrochemical sensing technology
- Flame-proof housing
- Suitable for indoor/outdoor applications
- Two-wire 4-20mA loop powered
- Non-intrusive configuration
Specifications
Specifications
Use |
Rugged and reliable gas detector for the protection of personnel from toxic and oxygen gas hazards. Suitable for use in Zone 1 or 2 hazardous areas and North American Class I and II Division 1 or 2 areas. |
---|---|
Connections and Power |
2-wire loop powered; 17Vdc (+/-10%) to 24Vdc (max) operation; 22mA max. over range |
Recommended Cable |
2-wire with shield (90% coverage) or conduit; 0.5mm2 (20AWG) to 2.0mm2 (14AWG) |
Singal |
0-100%FSD 4-20mA; Fault = 3mA; Calibration due selectable off or 3mA Max. over range 22mA; Inhibit (toxic sensors) = Selectable 3mA or 4mA Inhibit; (Oxygen sensors) = Selectable 3mA or 17.4mA |
Material |
|
Maximum Dimensions |
164 x 201 x 99mm |
Weight |
Aluminum alloy: 3.75 lbs./1.79 kg |
IP Rating |
IP66 (EN60529), NEMA 4X |
Operating Humidity |
Continuous 20-90% RH (non-condensing); Intermittent 0-99% RH (non-condensing) |
Operating Pressure |
90-110kPa |
Storage Conditions |
15°C to 30°C |
Sensor Specs
Sensor Specifications
Gas | Range |
---|---|
O2 | 25% vol |
CO | 100 to 1,000 ppm |
H2S (Low Range) | 10 to 50 ppm |
H2S (High Range) | 50 to 500 ppm |
CL2 | 5 to 20 ppm |
O3 | 0 to 0.4 ppm |
SO2 | 5.0 to 20.0 ppm |
ClO2 | 0 to 1 ppm |
NO | 0-100 ppm |
NO2 | 5 to 50 ppm |
H2 | 0 to 1000 ppm |
H2 (High Range) | 0 to 10,000 ppm |
HCl | 10 to 20 ppm |
HCN | 0 to 20 ppm |
HF | 0 to 12 ppm |
NH3 | 50 to 200 ppm |
NH3 | 200 to 1,000 ppm |
PH3 | 0 to 1.2 ppm |
Accessories

Series 3000 Mkll and Mklll Calibration Cap
Part Number: S3KCAL

Series 3000 Mkll and Mklll Collecting Cone
Part Number: S3KCC

Series 3000 Mkll and Mklll Duct Mounting Kit
Part Number: S3KDMK

Series 3000 Mkll and Mklll Remote Mounting Kit
Part Number: S3KRMK