Sales & Support 1300 436 267
Sensepoint XCD Gas Detection Transmitter

Sensepoint XCD Toxic, O2 and Flammable Transmitter

Sensepoint XCD now has remote monitoring capabilities for its toxic and Oxygen sensors. Its remote capability is designed to offer excellent flexibility of use and is an ideal solution for hard-to-reach locations or areas where the transmitter needs to be separate from the sensor. With remote toxic and Oxygen sensor mounting of up to 30m away from the transmitter. Sensepoint XCD provides a robust monitoring solution even in challenging environments where detection is difficult, including applications where the point of detection is in an area that is not easily accessible or where the detector would not be visible, like in high or low level concealed areas or outside a room being monitored.

A tri-color backlit LCD clearly indicates the unit's status at a glance, even from a distance. A steady green backlight indicates normal operation, flashing yellow indicates fault and flashing red indicates an alarm.

All detectors are supplied pre-configured and include two programmable alarm relays, one programmable fault relay as well as an industry standard 4-20mA output (sink or source selectable) and MODBUS communication. The scale, range, relay operation, alarm set point and electronic tag number of the detector can be adjusted using the transmitter's LCD and non-intrusive magnetic switches. Outputs are automatically inhibited during adjustment, thereby reducing the risk of false alarm at the control panel during maintenance.

Contact Us for stock levels and order fulfillment

Sales & Support: 1300 436 267
Email: [email protected]

Sensor Range

  • H₂S, 
  • CO, 
  • O₂, 
  • LEL, 
  • NO₂, 
  • H2, 
  • CO2.
  • Features
  • Specifications
  • Sensor Specs
  • Accessories
  • PDF Download

Features

  • Flammable (catalytic or infrared), toxic and oxygen versions available
  • Serves new/retrofit, indoor/outdoor applications
  • Stainless steel or aluminum explosion-proof housing options
  • IP66 as standard
  • All-in-one gas monitoring solution
  • Proven SurecellTM electrochemical sensors
  • Global approvals

Specifications

Specifications

Use

3 wire, 4-20mA and RS485 MODBUS output fixed point detector with in-built alarm and fault relays for the protection of personnel and plant from flammable, toxic and Oxygen hazards. Incorporates a transmitter with local display and fully configurable via non-intrusive magnetic switch interface

Input Voltage Range

12 to 32VDC (24VDC nominal)

Max Power Consumption

Maximum power consumption is dependent on the type of gas sensor being used. Electrochemical cells = 3.7W, IR = 3.7W and catalytic = 4.9W. Maximum inrush current = 800mA at 24VDC

Current Output Relays
  • Sink or source
  • Relays 3 x 5A@250VAC. Selectable normally open or normally closed (switch) and energized/de-energised (programmable)
  • Alarm relays default normally open/de-energized. Fault relay default normally pen/energized
Communication

RS485, MODBUS RTU

Material
  • Housing: Epoxy painted aluminium alloy ADC12 or 316 stainless steel
  • Sensor: 316 stainless steel
Weight (approx)

Aluminium Alloy LM25: 4.4lbs

316 Stainless Steel: 11lbs

Mounting

Integral mounting plate with 4 x mounting holes suitable for M8 bolts. Optional pipe mounting kit for horizontal or vertical pipe Ø1.5 to 3" (2" nominal)

Cable Entries

UL\cUL versions: 2 x ¾”NPT conduit entries. Suitable blanking plug supplied for use if only 1 entry used. Seal to maintain IP rating; ATEX/IECEx versions: 2 x M20 cable entries

IP Rating

IP66 in accordance with EN60529:1992

Certified Temperature Range

-40ºC to +65ºC

Sensor Specs

Sensor Specifications

Gas Range
O2 25% Vol.
H2S 10-100ppm
CO 100-1,000ppm
H2 1,000ppm
Flammable 1 to 8 (LEL) 20-100%LEL
Methane (LEL) 20-100%LEL
Propane (LEL) 20-100%LEL
CO2 2% vol

Accessories

Sensepoint XCD Duct mounting kit

Part Number: SPXCDDMK

Sensepoint XCD Mounting bracket

Part Number: SPXCDMTBR

Sensepoint XCD Sunshade / Deluge Protection

Part Number: SPXCDSDP